SJC Home
Clearance Sheet C2005-006930

 Department IssuesSigned OffIntl
These plans are for a interior buildout of a office/storage warehouse, reviewed using the 2004 Florida Fire Prevention Code. The plan is approved as submitted. 12/27/2005 PJW
The elevation of the floor surface on both sides of a door shall not vary by more than a 1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. NFPA 101 7.2.1.3. 12/27/2005 PJW
The following limits are placed on STORAGE OCCUPANCIES No STORAGE OF COMBUSTIBLES OF HIGH PILE STORAGE over 12 feet high? (NFPA 1, Chapter 8) No STORAGE OF COMBUSTIBLES 25 to 30 feet high? (NFPA 1, Chapter 8) No RUBBER TIRE STORAGE? (NFPA 1, Chapter 8) & (NFPA 231D) No RECORD STORAGE? (NFPA 1, Chapter 8) & (Record handling techniques that provide protection from fire shall comply with NFPA 232) No CELLULOSE NITRATE MOTION PICTURE FILM STORAGE? (NFPA 1, Chapter 8) & (Shall comply with NFPA 40) No AEROSOL PRODUCTS STORAGE? (NFPA 1, Chapter 9) & (shall comply with NFPA 30B) No FLAMMABLE AND COMBUSTIN\BLE LIQUID STORAGE? (NFPA 1, Chapter 17) & (Shall comply with NFPA 30) No STORAGE OF PORTABLE LP-GAS CONTAINERS INSIDE THE BUILDING? (NFPA 1, Chapter 24) & (NFPA 58) No STORAGE OF OXIDIZERS? (NFPA 1, Chapter 24) & (NFPA 430) No STORAGE OF ORGANIC PEROXIDES? (NFPA 1, Chapter 24) & (NFPA 432) Any storage of the above items may requi 12/27/2005 PJW
The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required. 12/27/2005 PJW
All doors that have dead bolts shall use thumb type single cylinder. 12/27/2005 PJW
Air handles with more than 2000 CFM is required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required) 12/27/2005 PJW
FYI:Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". 12/27/2005 PJW
Consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061) 12/27/2005 PJW