SJC Home
Clearance Sheet C2005-006219

 Department IssuesSigned OffIntl
Plans approved for a 1942 sq ft clubhouse. This was reviewed under the mercantile chapter due to occupancy load under 50 per FFPC 2004, NFPA 101. Occupancy load calculation is as follows: Exercise room w/equipt 4, Office 1, Kitchen 1, Great Room 39 (less concentrated) 10/20/2005 SLM
Kitchen has a stove on the plans. Per NFPA 1, 50.1.4, a commercial exhaust hood and suppression system will not be required if the stove is residential, at least one fire extinguisher is located in the kitchen, and this facility is not an assembly. Per NFPA 101, an assembly is an occupancy load 50 or more people. If at any time the occupancy load for this building has 50 or more people, or a commercial kitchen stove is installed, then a commercial exhaust hood and suppression system WILL BE REQUIRED. 10/20/2005 SLM
Consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061) 10/20/2005 SLM
FYI: Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial, and a minimum of 3-inches high for residential. These must be visible and legible from the street. 10/20/2005 SLM
All doors that have dead bolts shall use thumb type single cylinder. 10/20/2005 SLM
The elevation of the floor surface on both sides of a door shall not vary by more than a 1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. NFPA 101 7.2.1.3. 10/20/2005 SLM