Plan APPROVED for 8 foot kitchen exhaust hood. This is reviewed under 2010 Fl Fire Prevention Code.
A separate permit is required for the fire suppression system.
|
10/17/2013
| smurray |
|
|
For a point of information to the General Contractor, The Fire Marshals' Office requires that a fire inspector witness a light test of the duct from the hood through the roof before the duct is raised into the ceiling. Pass this on to your mechanical contractor for the hood.
|
10/17/2013
| smurray |
|
|
Consult with your fire extinguisher contractor for this special portable fire extinguisher requirement, pay special attention to the following requirement:
- mounted with in 30' travel distance of all cooking areas
- placards shall be conspicuously placed near the extinguiher that states, "FIRE PROTECTION SYSTEM SHALL BE ACTIVATED PRIOR TO USING FIRE EXTINGUISHER. (NFPA 1, 13.6.5.3.2)
|
10/17/2013
| smurray |