Please indicate the sub-classification of this Institutional Occupancy I-1, I-2 ?.
When the sub-classification of this structure is determined the review can be completed.

 

Please provide a summary of this structure meeting type II construction, type II construction is non-combustible.

 

Depending on the occupancy classification of this structure plumbing fixtures may need to be altered.

 

The screen porch on the plans will need to be accompanied with a different clearance sheet and an approved DRC site plan.

 

Provide shaft details for the grease duct serving a type 1 hood that is to penetrate the rated roof/ceiling assembly.

 

Unable to locate gas piping details or drawings.

 

Carbon monoxide alarms must be shown on plans as required by Florida Statute 553.885.