| | Department Issues | Signed Off | Intl |
|
|
Please indicate the sub-classification of this Institutional Occupancy I-1, I-2 ?. When the sub-classification of this structure is determined the review can be completed.
|
| |
|
|
Please provide a summary of this structure meeting type II construction, type II construction is non-combustible.
|
| |
|
|
Depending on the occupancy classification of this structure plumbing fixtures may need to be altered.
|
| |
|
|
The screen porch on the plans will need to be accompanied with a different clearance sheet and an approved DRC site plan.
|
| |
|
|
Provide shaft details for the grease duct serving a type 1 hood that is to penetrate the rated roof/ceiling assembly.
|
| |
|
|
Unable to locate gas piping details or drawings.
|
| |
|
|
Carbon monoxide alarms must be shown on plans as required by Florida Statute 553.885.
|
| |