Plan approved to modify 23 heads in existing bldg with existing sprinkler system.

12/13/2007 SLM
Sprinkler modifications exceeding 20 heads shall be isolated and tested at 200 psi for 2 hours. Modifications that cannot be isolated and sprinkler modifications less than 20 heads, shall be tested at system working pressure. (NFPA 13: 16.2.1.4, 16.2.1.5, and 16.2.1.6) 12/13/2007 SLM