Clearance Sheet C2005-003790*001

 Department IssuesSigned OffIntl

Plan APPROVED for 2500 sq ft IBO of existing space in a 3 story bldg protected by fire sprinklers and fire alarm. This was reviewed under 2004 Fl Fire Prevention Code as business.

10/26/2007 SLM
The scope of work for this project is in the area of an existing fire sprinkler and fire alarm system. A separate fire sprinkler AND fire alarm permit is required for any modification to this system. A hold is placed on the Building Permit and no inspections will be done until this Fire Sprinkler and fire alarm Permit is submitted & approved. (NFPA 1,13.1.1.1) 10/26/2007 SLM
Consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061) 10/26/2007 SLM
All doors that have dead bolts shall use thumb type single cylinder. (NFPA 101, 7.2.1.5) 10/26/2007 SLM