These plans are for an interior buildout for Great Clips. The plans are APPROVED as submitted.
|
4/29/2005
| PJW |
|
|
3. The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required.
|
4/29/2005
| PJW |
|
|
All doors that have dead bolts shall use thumb type single cylinder.
|
4/29/2005
| PJW |
|
|
FYI: Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s).
|
4/29/2005
| PJW |
|
|
Please consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061)
|
4/29/2005
| PJW |