| | Department Issues | Signed Off | Intl |
|
|
1)HOLD 102--The French doors added do not meet egress requirements per 1005.2 of the 2010 FBC, please address this issue and provide a life safety plan showing egress requirements.
|
4/8/2015
| blaw |
|
|
2)HOLD 102-- The electrical pages indicate that the break room will have a dishwasher, sink and microwave please remove these references to this per phone conversation with the architect.
|
4/8/2015
| blaw |
|
|
3)HOLD 100-- Please provide a product approval number on the French door added or whatever configuration is achieved to meet egress per comment 1.
|
4/14/2015
| blaw |
|
|
4)HOLD 100-- weld certification for truss reinforcing of roof top units
|
4/14/2015
| blaw |