Plan APPROVED for 32653 sqft remodel of former furniture store for a new mattress store protected with fire sprinkler system and fire alarm system. This is reviewed under Fl Fire Prevention Code 5th edition as mercantile.
|
3/16/2015
| SMurray |
|
|
The scope of work for this project is in the area of an existing fire sprinkler system. A separate fire sprinkler permit is required for any modification to this system. A hold is placed on the Building Permit and no inspections will be done until this Fire Sprinkler Permit is submitted & approved. (NFPA 1,13.1.1.1)
|
3/16/2015
| SMurray |
|
|
Locks on exit doors or access exit doors shall not require the use of a key, a tool, or special knowledge or effort for operation from the egress side unless they meet the requirements of NFPA 101, 7.2.1.5.
|
3/16/2015
| SMurray |
|
|
Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". (NFPA 1, 10.12.1.2)
|
3/16/2015
| SMurray |
|
|
FS 633.061 requires a license or permit of organizations & individuals who: service, recharge, test, mark, inspect, install or hydrotest fire extinguishers. It will be necessary to use a Licensed Fire Extinguisher Contractor for identifying the location & type of extinguisher to use.
|