This is a major revision to the approved set of plans. Each page revised has the revision # and date identified on each page.
The plans are approved with one comment added to the plans:
1. Page E2.1 - E2.4, The room housing the Fire Alarm Control Panel (FACP) needs to be climate controled. This is not identiifed on any of the M- series of plans or within the E series of plans. Please provide details as to how this will be done. This action will require a separate revision to the plans.
|