Plans approved for a clubhouse. Assembly chapter was used to review.
|
5/11/2005
| SLM |
|
|
The Grease Exhaust Hood noted on this page and several other pages throughout these plans are conceptual. A separate permit will be required by the Fire Marshal. A HOLD will be placed on the building permit and NO FRAMING INSPECTION will be done until this permit is submitted & approved.
|
5/11/2005
| SLM |
|
|
The Grease Exhaust Hood requires a FIRE SUPPRESSION SYSTEM. The Fire Marshal's Office requires a separate permit and a HOLD will be placed on the building permit whereby NO FRAMING INSPECTION AND NO FINAL EXHAUST HOOD INSPECTION can be done until this permit is approved.
|
5/11/2005
| SLM |
|
|
Consult with your fire extinguisher contractor for the portable fire extinguisher requirement, pay special attention to the requirement of a K type extinguisher that is required in the cooking area.
|
5/11/2005
| SLM |
|
|
Please post the Occupant Load in a visible location within the building.
|
5/11/2005
| SLM |
|
|
Panic hardware required due to occupancy load over 100 people.
|
5/11/2005
| SLM |
|
|
Locks on gates coming from the pool shall meet NFPA 101, 7.2.1.5.2.
|
5/11/2005
| SLM |
|
|
FIRE LANES shall be marked with free standing signs with the words "NO PARKING FIRE LANE BY ORDER OF THE FIRE DEPARTMENT." Such signs shall be 12" by 18" with a white background & red letters and shall be a minimum of 7-feet in height from the roadway to the bottom part of the sign. The sign shall be within sight of the traffic flow and be a maximum of 60 feet apart.(FPC 1.3.5.4)
|
5/11/2005
| SLM |