SJC Home
Clearance Sheet C2005-001743*009

 Department IssuesSigned OffIntl
General Notes: Your re-submittal shall include three complete sets of plans. Please insert the revised pages into the plan sets, and pages removed from the stamped "Job copy" set, shall be resubmitted marked as "old set" and shall be included in the re-submittal. If old "Job copy" drawings, are not resubmitted there will be additional plan review fee charged due to the amount of time necessary to review entire drawing again. ALL ITEMS REVISED SHALL BE IDENTIFIED. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW AS PER ORDINANCE # 98-42 “An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged. PORTOFINO AT WETPARC Clubhouse See attached list. Arch. Firm: Bessolo Design Group St. Pete, FL. Arch. Name: Kevin J. Bessolo (Talked with Rick Tralior) Phone: 727-894-4453 Lic. # AR12069 Stru. Eng.: KEM Engineers, Inc. Stru. Name: Phone # Lic. # Mech. Eng. Name: Phone # Lic. # Elec. Eng. Name: Phone # Lic. # FBC 2001 Code Building Use: ? Occp. Type: ? Occp. Load: Const. Type: Spkl.: Stories: 1 Allow. Hts. & Area (Tbl. 500): sq. ft. Fire Protection: (Tbl. 600): Int. Bearing Walls 1 hr. Int. Non-bearing Walls: 1 hr. Columns: 1 hr. Beams, Girders, Trusses: 1 hr. Floor & Ceiling Assemblies: 1 hr. Roof Assemblies: 1 hr. Ext. Bearing Walls: 1 hr. 0-3’ (0% openings) Ext. Non-bearing Walls: 1 hr. 0-3’ (0% openings) Area Separation: no calculations presented Occp. Separation: 1 hr. Tenant Separation: 1 hr Sect. 704.3 Rated Corridors: Floor Area 1st: varies Designed: Partially Enclosed Exposure: B Top Chd. DL: Roof: Fiberglass shingle  
1. Submit is incomplete as per Section 104.3.1.1 FBC 2001. Drawings are incomplete for Mechanical as well as Plumbing including but not limited to water supply lines, hoods, grease traps, etc.  
2. Provide a code analysis for the Clubhouse buildings of this project. (occupancy, construction type, fire protection requirements, protected/unprotected, wind loads, pressures for opening, area and height limitation, and square footage of buildings as per section 104.3.1.1 FBC.) Please define the any rated separations that will be required as per occupation construction type, etc.  
3.This review will be for the Clubhouse building on the site inclusive of Residential buildings, Garages, gazebos and any other accessory structures, including courts. See attached list.  
4. As per Section 11-4.3.2 FACBC, Indicate at least one accessible route within the boundary of the site from a public way and connecting all accessible buildings on the site.  
5. As per Section 11-4.29.5 FACBC, Provide detectable warnings at Hazardous Vehicular area at any walks that cross or adjoin a vehicular way.  
6. Correlate foundation plans drawn by Trillium with the structural plans by KEM and the architectural plans by Besso. Please clarify location, size and details for all footers, pads, and slabs as there seems to be some discrepancies. See columns, pads, interior shear walls, and configuration of walls at breezeways, slab and pool deck. Please show full section indicating that clubhouse will meet the angle of repose for the pool.  
7. Foundation plans shall be approved by the Designer of Record.  
8. Please provide sheet PT-01 as indicated in Notes on Sheet ST-02 - ST-06.  
9. Correlate structural plans with architectural plans for separation of rated walls. Show complete exterior and interior wall sections from the foundation through the roof framing with all ratings as per table 600.  
10.Several assemblies (P522, P550 & GA File No. WP-8105) are listed on Sheet A 8.5.1, please indicate where this are being used.  
11. Rating for GA File No. WP-8105 appears to be out of date as it is not listed in the current GA filing. Please correct and resubmit.  
12. The SBC code is no longer an acceptable code please change the general notes to reflect such.  
13. As required by the Board of Engineers a letter or other document must be submitted indicating the Engineer of Record has reviewed the truss submittal package. The truss layout {truss placement plan} shall be reviewed, approved and signed by the building designer stating essentially the following: “The building designer has reviewed the truss drawings and truss placement plan(s) and said drawings and plans meet with his/her design.”  
14. Truss connectors shall be the Designer of Record and shall correlate to the truss layout and truss data sheets. Please correlate plans as it appears there are no trusses for the car wash area. No further review on trusses.  
15. Where is note 6 referred to on Truss strap schedule?  
16. Please change Handicap notes to reflect FACBC 2001 not GAC.  
17. Please specify limitations of use in Product Approval matrix.  
18. The occupancy load Table appears incorrect. Show equipment in fitness room or use 15 ft. Assuming the seating in the theater is fixed as shown, please use correct count.  
19. Submit Hood drawings for stove.  
20. A service sink will be required for the activity center, please show location.