| | Department Issues | Signed Off | Intl |
|
|
Plans approved for condos. Apt chapter used for review.
|
5/11/2005
| SLM |
|
|
The Fire Sprinkler information provided in these plans are conceptual. A separate fire sprinkler permit is required by the Fire Marshal. A HOLD will be placed on the building permit and no framing inspection will be done until this permit is submitted & approved.
|
5/11/2005
| SLM |
|
|
The UNDERGROUND CONTRACTOR for the installation & hydro test of the fire sprinkler line will require a separate permit. A HOLD will be placed on the building permit and NO FIRE SPRINKLER FINAL will be done until this permit is submitted & approved.
|
5/11/2005
| SLM |
|
|
Any reference to the Fire Alarm in these plans are conceptual. A separate permit is required by the Fire Marshal. A HOLD will be placed on the building permit and NO FRAMING INSPECTION will be done until this permit is submitted & approved.
|
5/11/2005
| SLM |
|
|
Provide a EMERGENCY ACCESS KEY BOX near the main entrance. This box is required because there is a fire sprinkler riser located inside this building. An authorization form for the Knox Box can be obtained at the Fire Marshal's Office.(4455 Avenue "A", Suite 100, St Augustine, Phone 904-823-2709)
|
5/11/2005
| SLM |
|
|
FYI: Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s).
|
5/11/2005
| SLM |
|
|
FIRE LANES shall be marked with free standing signs with the words "NO PARKING FIRE LANE BY ORDER OF THE FIRE DEPARTMENT." Such signs shall be 12" by 18" with a white background & red letters and shall be a minimum of 7-feet in height from the roadway to the bottom part of the sign. The sign shall be within sight of the traffic flow and be a maximum of 60 feet apart.(FPC 1.3.5.4)
|
5/11/2005
| SLM |
|
|
Please label roof access.
|
5/11/2005
| SLM |
|
|
Provide smoke dets outside every sleeping area and every level.
|
5/11/2005
| SLM |
|
|
Please consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061)
|
5/11/2005
| SLM |