SJC Home
Clearance Sheet C2005-001743*007

 Department IssuesSigned OffIntl
Plans approved for condos. Apt chapter was used for review. 5/11/2005 SLM
The Fire Sprinkler information provided in these plans are conceptual. A separate fire sprinkler permit is required by the Fire Marshal. A HOLD will be placed on the building permit and no framing inspection will be done until this permit is submitted & approved. 5/11/2005 SLM
The UNDERGROUND CONTRACTOR for the installation & hydro test of the fire sprinkler line will require a separate permit. A HOLD will be placed on the building permit and NO FIRE SPRINKLER FINAL will be done until this permit is submitted & approved. 5/11/2005 SLM
Any reference to the Fire Alarm in these plans are conceptual. A separate permit is required by the Fire Marshal. A HOLD will be placed on the building permit and NO FRAMING INSPECTION will be done until this permit is submitted & approved. 5/11/2005 SLM
Provide a EMERGENCY ACCESS KEY BOX near the main entrance. This box is required because there is a fire sprinkler riser located inside this building. An authorization form for the Knox Box can be obtained at the Fire Marshal's Office.(4455 Avenue "A", Suite 100, St Augustine, Phone 904-823-2709) 5/11/2005 SLM
FYI: Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s). 5/11/2005 SLM
FIRE LANES shall be marked with free standing signs with the words "NO PARKING FIRE LANE BY ORDER OF THE FIRE DEPARTMENT." Such signs shall be 12" by 18" with a white background & red letters and shall be a minimum of 7-feet in height from the roadway to the bottom part of the sign. The sign shall be within sight of the traffic flow and be a maximum of 60 feet apart.(FPC 1.3.5.4) 5/11/2005 SLM
Please label roof access. 5/11/2005 SLM
Provide smoke dets outside every sleeping area and every level. 5/11/2005 SLM
Please consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061) 5/11/2005 SLM