Clearance Sheet C2005-000649*001

 Department IssuesSigned OffIntl
These plans are for a 5600 square foot restaurant, reviewed using the New Assembly Occupancy Chapter of the 2004 Florida Fire Prevention Code. The plans are APPROVED. 9/26/2005 PJW
The kitchen exhaust hood, and fire suppression system have not yet been recieved and each require a seperate permit. A HOLD will be placed on the master permit and NO INSPECTIONS from the building department of fire marshal's office will be performed until these are submitted. 9/26/2005 PJW
FYI: The elevation of the floor surface on both sides of a door shall not vary by more than a 1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. NFPA 101 7.2.1.3. 9/26/2005 PJW
FYI: The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required. 9/26/2005 PJW
FYI: All doors that have dead bolts shall use thumb type single cylinder. 9/26/2005 PJW
FYI: Air handles with more than 2000 CFM is required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required) 9/26/2005 PJW
FYI: Consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061) 9/26/2005 PJW
FYI: Consult with your fire extinguisher contractor for the portable fire extinguisher requirement, pay special attention to the requirement of a K type extinguisher that is required in the cooking area. 9/26/2005 PJW
FYI: Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial, and a minimum of 3-inches high for residential. These must be visible and legible from the street. 9/26/2005 PJW