These plans are for a 5600 square foot restaurant, reviewed using the New Assembly Occupancy chapter of NFPA 101 2000 edition referenced by 69A-55 (The uniform fire safety standards for public food service establishments) The plan is NOT APPROVED, PENDING. The fire sprinkler modification, the kitchen exhaust hood, and the fire suppression system require 3 different permits to be pulled through the building department.  
Panic hardware is required on the all dining room doors as marked on the plans per NFPA 101 12.2.2.2.3. This includes the main entrance/exit.  
The elevation of the floor surface on both sides of a door shall not vary by more than a 1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. NFPA 101 7.2.1.3.  
3. The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required.  
All doors that have dead bolts shall use thumb type single cylinder.  
Air handles with more than 2000 CFM is required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required)  
FYI: Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial, and a minimum of 3-inches high for residential. These must be visible and legible from the street.  
Consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061)  
Consult with your fire extinguisher contractor for the portable fire extinguisher requirement, pay special attention to the requirement of a K type extinguisher that is required in the cooking area.