Clearance Sheet C2005-000413*008

 Department IssuesSigned OffIntl

Plan reviewed for build out of 1340sf assembly in an existing construction type IIB fire sprinklered building separated from neighboring spaces by 1hr tenant separation wall on either side. Reviewed as new assembly using FFPC 6th edition effective Dec. 31, 2017.

Reviewer: 
V.Vitori 904 209 1748

 
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1.
Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.

12/12/2019 VVitori

INFORMATIONAL ONLY NO RESPONSE NECESSARY:
The system(s) outlined in this set of plans is conceptual.

A HOLD has been placed at framing (105) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:

- fire sprinkler system

12/12/2019 VVitori

Rear exit access door not labeled. A direction indicator showing the direction of travel, shall be placed in every location where the direction of travel to reach the nearest exit is not apparent. 101:7.10.2.1

12/12/2019 VVitori

At the time of fire final be prepared to provide a copy of the manufacturer specification sheets to the fire inspector showing that each interior finish will meet:

- wall and ceiling finish will meet Class A, B or C. 101:12.3.3.3.

- floor finish shall meet either: a) ASTM D 2859 for carpet and carpet like materials or b) has a minimum critical radiant flux of .1 W/cm2 for non carpet flooring. 101:12.3.3.5.3.

If there are multiple finishes, label each spec sheet identifying each product, its location AND highlight the area showing illustrating it meets the applicable Code requirement.

12/12/2019 VVitori
Any assembly room/space without fixed seating and that is over 50 will need to be posted at the final.

The occupant load shall be posted in a conspicuous place near the main entrance/exit from the room. The Posting should read,"Maximum Occupant Load ______ Persons, by order of the Fire Marshal"  NFPA 101 12/13.7.9.3
12/12/2019 VVitori