Your re-submittal shall include three complete sets of plans. Or you may remove and insert the corrected revised pages into the plan sets. The "JOB COPY" set of the original drawing shall be included in the re-submittal. ALL ITEMS REVISED SHALL BE IDENTIFIED.
ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW
AS PER ORDINANCE # 98-42 “An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.
Arch.Name: Forum Architecture – R. Norman Stoehr
Phone # 407-830-1400 Lic. # AR009930
Stru Eng.Name: R.L.Plowfield Assoc. –Robert L. Plowfield Jr.
Phone # 407-657-6657 Lic. # 39759
Mech. Eng.Name: Phone # Lic. #
Elec. Eng.Name: Phone # Lic. #
Building Use: Vacation Timeshare Occp Type: R-1 Occp. Load:
Const. Type: V Unprotected Spkl.: YES Stories: 5
Area Separation: Occp. Separation Rated Corridors:
Floor Area 1st :7200 2nd-5th 6896.5
05-06-05wjd
There has been a change to the design parameters.
|
2/2/2006
| WJD |
|
|
1. Sheet Code Compliance Sheet TS A1.02 refers to the design of the windloads to be to 2000 Edition of the International Building Code. Please design to the current building Coded FBC 2001 for all aspects and to the NEC 2002 and 2001 FACBC for Accessibility.
|
5/6/2005
| WJD |
|
|
2. The plans can not meet the necessary requirement for a type IV construction FBC 2001. (wood trusses) This review has been done assuming the structure can be designed to a type V protected and sprinkled. Please correct code compliance sheet or submit plans that comply with a type IV construction.
05-06-05wjd
Please change the Type of Construction indicated on Life Safety plan Sheet A1.10 to reflect the current changes to the design.
|
2/2/2006
| WJD |
|
|
3.The Code Compliance Sheet TS A1.02 refers to 0 hours for interior non-bearing, please submit how sections 609.2, 704.1, 704.2 and 705.2 can be overcome.
05-06-05wjd
Please change table on Sheet A1.02 to reflect changes from protected to unprotected as well as Type of Construction indicated on Life Safety plan Sheet A1.10.
|
2/2/2006
| WJD |
|
|
4.Please check chart indicating Handicapped accessible units which must contain Florida's 5% rule as per Section 11-9.1.2 FACBC 2001 (Shaded text.)
05-06-05wjd
Sheet A5.01 and all other floor plans shall reflect the layouts shown for accessibily as indicated on A5.08 and A5.09. Also please make sure that all details and section numbers on the handicapped pages are correct, some indicate the wrong page number.
|
2/2/2006
| WJD |
|
|
5. This is a Threshold Building. Please submit name and license number of the Threshold inspector.
05-06-05wjd
This item has not been addressed. Please submit requested information prior to obtaining building permit.
|
2/2/2006
| WJD |
|
|
6. This is a Threshold Building. Please submit shoring and reshoring plans as per Section 105.13.4.2 FBC 2001.
05-06-05wjd
This item has not been addressed. Please reference Florida Statues 553.79 (5). See attached copy.
|
2/2/2006
| WJD |
|
|
7. This is a Threshold Building. EVERY Structural page of the plans must contain a statement by the Designer of Record indicating (to the best of the architects' or engineers' knowledge, the plans and specifications comply with the applicable minimum building codes and the applicant fire safety standards as determined by the local authority in accordance with this section and 633 Florida Statues.) Section 105.13.4.4.
|
5/6/2005
| WJD |
|
|
8. Access openings to refuse and laundry chute shall not be located in exit access corridors or exit enclosures. Section 705.2.4.3 FBC 2001.
|
5/6/2005
| WJD |
|
|
9. Openings within 10 ft horizontal extension of the protected walls beyond the stairway shall be equipped with fixed 3/4 hour assembles. Section 1006.2.4 FBC 2001
05-06-05wjd
The exception mentioned in your comment does not allow for openings to be unprotected (referring to window D in the Lock out unit). Please see attached commentary sheet as a reference of intent.
|
2/2/2006
| WJD |
|
|
10. Please clarify all drawings to indicate that the stairways lead directly to the street or open space as per Section 1006.2.4 FBC 2001 Some plans indicate what may be a rail between elevator and stairs area on the first floor. Some indicate that there is no rail on the upper floor. The Life Safety plan indicates that exit is through the Elevator lobby area, if this is your intent please review Section 1010.3 FBC 2001.
|
5/6/2005
| WJD |
|
|
11. The fifth floor plans need some clarity. The life safety plan indicates rated walls that are not shown on other plans. Please clarify the occupancy load and indicate how this was calculated. Table 1003.1 FBC 2001 There shows a waiting area, a sales area, which tend to indicate different functions. Please further define the use of the area between the private office and the conference room. Some plans indicate seating arrangements in some areas and open in others.
05-06-05wjd
Still not total clarity here. Your written comments suggest that this area has been reworded. Reference to change of name to lobby on Sheet A5.05, however I don't see this. In addition, please clarify the table occupancy loads on Sheet A1.10, I believe that your calculations are incorrect.
The calculations indicate that this floor will be considered Small Assembly and therefore need 2 hour separation between all residential as per Section 704.1
|
2/2/2006
| WJD |
|
|
12. As per table 403.1 FPC 2001 Drinking fountain(s) must be provided on the fifth floor, and shall meet FACBC requirements. See section 11-4.1.(10)FAC. Must have a "hi-lo" fountain or provide two fountains.
|
5/6/2005
| WJD |
|
|
13. The Plumbing risers do not indicate the same amount or type of fixtures indicated on the plans, please correct.
05-06-05wjd
This item has not been addressed.
Please correlate all tags on plans to the waste and vent riser diagrams as shown on Sheet 14.01, .02, & .03.
|
2/2/2006
| WJD |
|
|
14. Indicate correct venting for 4S1, 3S, 4S, & 5SA risers. Section 903 FPC 2001
|
5/6/2005
| WJD |
|
|
15. Notation: Dryer vents exceeding 25' as per the requirement of Section 504.6 FMC 2001 shall have the dryer in place before C.O. and manufacture data sheet indicating compliance with code.
|
5/6/2005
| WJD |
|
|
16. Submit all details and calculations for room where water heaters are located. Shall include at least requirements for wall rating, egress requirements, manufactured data, combustible air requirements and ventilation.
|
5/6/2005
| WJD |
|
|
17. Please label all doors and windows shown on plans, and include hardware schedule to indicate any fire or ADA requirements that maybe necessary.
05-06-05wjd
Please see item 9 for window rating.
|
2/2/2006
| WJD |
|
|
18. There is no Sheet I/S5.01 as mentioned on Sheet TS S404.
05-06-05wjd
Please change note number 9 on Sheet S4.04 to reflect 1/S4.21
|
2/2/2006
| WJD |
|
|
19. There is no detail on Sheet H15.06 for item #11 as indicated on Sheet M 15.04
05-06-05wjd
This item not addressed.
I don't see any "Wall mount AHU detail on Sheet H15.06 as referenced by note #11.
Please submit manufacture data sheets for Package hung units (see PTAC-1 linen room) that are mounted on a rated wall so fire damper in wall unit can be verified.
|
2/2/2006
| WJD |
|
|
20. There is no Sheet P3.03 as mentioned on Sheet P14.05 referring to Gas riser.
|
5/6/2005
| WJD |
|
|
21. Truss index sheet shall be sealed and signed by specified Delegated Engineer (Truss designer) Edmond R Stanton. Also this sheet shall reference St. Johns County not Flagler County.
05-06-05wjd
Item not addressed.
|
2/2/2006
| WJD |
|
|
22. Please clarify notation on Sheets S 401 and S404 as to correlate of type of clips. (Reference H clips)
|
5/6/2005
| WJD |
|
|
23. Truss connectors for trusses R 47 and R 10 do not meet the designed uplift as supplied by truss manufacture.
05-06-05wjd
Item not addressed.
|
2/2/2006
| WJD |
|
|
24. Truss data sheets and truss layout need to correlate. Quantity shown for Truss R3 appears incorrect. Can't find truss R51 on truss layout. Can't find truss data sheet for R 57 shown on layout.
|
2/2/2006
| WJD |
|
|
25. Product of approval needs to specify limitations of use. In addition, please specify M.D. NOA number for soffit.
05-06-05wjd
Item not addressed.
|
2/2/2006
| WJD |
|
|
26. A general purpose outlet shall be in the quipment rrom on first floor. per Joe daCosta
|
| |
|
|
There is a change of valuation. The Building Valuation is
based on the data compiled by SBCCI & ICC using the Marshall Valuation
Service as published by the Marshall and Swift Publication Company
and printed in the Southern Builder.
$4,568,095.57
|
5/6/2005
| WJD |
|
|
26. Submit all fire resistant materials construction assemblies of constructions as listed in 709.7 or acceptable publications. 701.5.2 FBC 2001. Not limited to the following: Submit RC 2601 as cannot find current acceptance to GA#2601 which as shown is for 2 x 10 joist not prefab trusses; Submit all for Rinker Block. Submit UL u438, and J901.
05-06-05wjd
Item not totally addressed. Please supply documentation from Rinker Block concerning their rating.
|
2/2/2006
| WJD |
|
|
27. Extended walls on the balconies shown on sheet A 505, 506 & 506 shall be rated as per Section 7044.5 FBC 2001.
|
5/6/2005
| WJD |
|
|
28. The two bedroom master plan with shower will need an additional exhaust fan due to moisture.
05-06-05wjd
I cannot find B5-H15.04 or B6, no changes have been made to electrical plans.
|
2/2/2006
| WJD |
|
|
29. Cannot find H15.07 as indicated next to detail on Sheet E16.03
|
5/6/2005
| WJD |