| | Department Issues | Signed Off | Intl |
|
|
General Notes:
Your re-submittal shall include three complete sets of plans. Or you may remove and
insert the corrected revised pages into the plan sets. The job set of the original drawing
shall be included in the re-submittal. ALL ITEMS REVISED SHALL BE IDENTIFIED.
ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS
SUBMITTED FOR REVIEW
AS PER ORDINANCE # 98-42 “An additional fee due and payable at permitting shall be of
$100 each for any second resubmission of plans. Per FL. Statute 553.80(2)(b), on any
third and subsequent resubmissions that do not correct a code violation that is
specifically and continuously noted in each previous rejection, a fee of four times the
amount of the fee attributed to plan review will be charged.
Arch.Name: Forum Architecture – R. Norman Stoehr
Phone # 407-830-1400 Lic. # AR009930
Stru Eng.Name: R.L.Plowfield Assoc. –Robert L. Plowfield Jr.
Phone # 407-657-6657 Lic. # 39759
Mech. Eng.Name: Phone # Lic. #
Elec. Eng.Name: Phone # Lic. #
Building Use: Vacation Timeshare Occp Type: R-1 Occp. Load:
Const. Type: V Unprotected ???? Spkl.: YES
Stories: 5
Area Separation: Occp. Separation Rated
Corridors:
Floor Area 1st-7200' 2nd-6896.5' 3rd-6896.5' 4th-6896.5' 5th-6896.5' TOTAL 34,796 sq. ft. Gross area
|
2/2/2006
| WJD |
|
|
There is a change of valuation. The Building Valuation is
based on the data compiled by SBCCI & ICC using the Marshall Valuation
Service as published by the Marshall and Swift Publication Company
and printed in the Southern Builder.
$3,293,764.38
|
5/9/2005
| WJD |
|
|
1. Sheet Code Compliance Sheet TS A1.02 refers to the design of the windloads to be to
2000 Edition of the International Building Code. Please design to the current building
Coded FBC 2001 for all aspects and to the NEC 2002 and 2001 FACBC for Accessibility.
7/14/05wjd This was signed off by mistake
Please change ICC Accessibility to FACBC 2001 for Accessibility
|
5/9/2005
| WJD |
|
|
2. The plans can not meet the necessary requirement for a type IV construction FBC 2001.
(wood trusses) This review has been done assuming the structure can be designed to a type
V protected and sprinkled. Please correct code compliance sheet or submit plans that
comply with a type IV construction.
05-09-05wjd
Please change the Type of Construction indicated on Life Safety plan Sheet A1.10 to
reflect the current changes to the design.
07-14-05wjd
Please correltate plans - Is the design a 1 hr protected as shown in table anc called out on TS A1-10 OR unprotected as called out in "Code Compliance" and "Code Compliance for Time Share Buildings" (but table shows 1 hr)?
Please correct and resubmit.
|
2/2/2006
| WJD |
|
|
3.The Code Compliance Sheet TS A1.02 refers to 0 hours for interior non-bearing, please
submit how sections 609.2, 704.1, 704.2 and 705.2 can be overcome.
05-09-05wjd
Please change table on Sheet A1.02 to reflect changes from protected to unprotected as
well as Type of Construction indicated on Life Safety plan Sheet A1.10.
07-14-05 wjd
Please see previous comment item number 2
|
2/2/2006
| WJD |
|
|
4.Please check chart indicating Handicapped accessible units which must contain Florida's
5% rule as per Section 11-9.1.2 FACBC 2001 (Shaded text.)
05-09-05wjd
Sheet A5.01 and all other floor plans shall reflect the layouts shown for accessibily
as indicated on A5.08 and A5.09. Also please make sure that all details and section
numbers on the handicapped pages are correct, some indicate the wrong page number.
|
7/14/2005
| WJD |
|
|
5. This is a Threshold Building. Please submit name and license number of the Threshold
inspector.
05-09-05wjd
This item has not been addressed. Please submit requested information prior to
obtaining building permit.
|
7/18/2005
| WJD |
|
|
6. This is a Threshold Building. Please submit shoring and reshoring plans as per Section
105.13.4.2 FBC 2001.
05-09-05wjd
This item has not been addressed. Please reference Florida Statues 553.79 (5). See
attached copy.
|
7/18/2005
| WJD |
|
|
7. This is a Threshold Building. EVERY Structural page of the plans must contain a
statement by the Designer of Record indicating (to the best of the architects' or
engineers' knowledge, the plans and specifications comply with the applicable minimum
building codes and the applicant fire safety standards as determined by the local
authority in accordance with this section and 633 Florida Statues.) Section 105.13.4.4.
|
5/9/2005
| WJD |
|
|
8. Access openings to refuse and laundry chute shall not be located in exit access
corridors or exit enclosures. Section 705.2.4.3 FBC 2001.
|
5/9/2005
| WJD |
|
|
9. Openings within 10 ft horizontal extension of the protected walls beyond the stairway
shall be equipped with fixed 3/4 hour assembles. Section 1006.2.4 FBC 2001
05-09-05wjd
The exception mentioned in your comment does not allow for openings to be unprotected
(referring to window D in the Lock out unit). Please see attached commentary sheet as a
reference of intent.
|
7/14/2005
| WJD |
|
|
10. Please clarify all drawings to indicate that the stairways lead directly to the street
or open space as per Section 1006.2.4 FBC 2001 Some plans indicate what may be a rail
between elevator and stairs area on the first floor. Some indicate that there is no rail
on the upper floor. The Life Safety plan indicates that exit is through the Elevator lobby
area, if this is your intent please review Section 1010.3 FBC 2001.
|
5/9/2005
| WJD |
|
|
11. Submit all fire resistant materials construction assemblies of constructions as listed
in 709.7 or acceptable publications. 701.5.2 FBC 2001. Not limited to the following:
Submit RC 2601 as cannot find current acceptance to GA#2601 which as shown is for 2 x 10
joist not prefab trusses; Submit all for Rinker Block. Submit UL u7438, and J901
05-09-05wjd
Still not total clarity here. Your written comments suggest that this area has been
reworded. Reference to change of name to lobby on Sheet A5.05, however I don't see this.
In addition, please clarify the table occupancy loads on Sheet A1.10, I believe that your
calculations are incorrect.
07-14-05wjd
Please submit a data sheet from Factory Mutual for FC-172.
|
2/2/2006
| WJD |
|
|
12. Extended walls on the balconies shown on sheet A 505, 506 & 506 shall be rated as per
Section 7044.5 FBC 2001.
|
5/9/2005
| WJD |
|
|
13. The Plumbing risers do not indicate the same amount or type of fixtures indicated on
the plans, please correct.
05-09-05wjd
This item has not been addressed. Please check 3S2 on all plans.
Please correlate all tags on plans to the waste and vent riser diagrams as shown on
Sheet 14.01, .02, & .03.
|
7/18/2005
| WJD |
|
|
14. The two bedroom master plan with shower will need an additional exhaust fan due to
moisture.
05-09-05wjd
I cannot find B5-H15.04 or B6, no changes have been made to electrical plans.
|
7/18/2005
| WJD |
|
|
15. Notation: Dryer vents exceeding 25' as per the requirement of Section 504.6 FMC 2001
shall have the dryer in place before C.O. and manufacture data sheet indicating compliance
with code.
|
5/9/2005
| WJD |
|
|
16. Submit all details and calculations for room where water heaters are located. Shall
include at least requirements for wall rating, egress requirements, manufactured data,
combustible air requirements and ventilation.
|
5/9/2005
| WJD |
|
|
17. Please label all doors and windows shown on plans, and include hardware schedule to
indicate any fire or ADA requirements that maybe necessary.
05-09-05wjd
Please see item 9 for window rating.
|
7/14/2005
| WJD |
|
|
18. There is no Sheet I/S5.01 as mentioned on Sheet TS S404.
|
5/9/2005
| WJD |
|
|
19. There is no detail on Sheet H15.06 for item #11 as indicated on Sheet M 15.04
|
5/9/2005
| WJD |
|
|
20. There is no Sheet P3.03 as mentioned on Sheet P14.05 referring to Gas riser.
|
5/9/2005
| WJD |
|
|
21. Truss index sheet shall be sealed and signed by specified Delegated Engineer (Truss
designer) Edmond R Stanton. Also this sheet shall reference St. Johns County not Flagler
County, any handwritten changes shall be initialed by the Designer.
05-09-05wjd
Item not addressed.
07-18-05wjd
As required by the Board of Engineers a letter or other document must be submitted indicating the Engineer of Record has reviewed the truss submittal package. The truss layout {truss placement plan} shall be reviewed, approved and signed by the building designer stating essentially the following: “The building designer has reviewed the truss drawings and truss placement plan(s) and said drawings and plans meet with his/her design.” The newly submitted truss layout and index data sheets are not approved by the EOR.
|
2/2/2006
| WJD |
|
|
22. Please clarify notation on Sheets S 401 and S404 as to correlate of type of clips.
(Reference H clips)
|
5/9/2005
| WJD |
|
|
23. Truss connectors for trusses R 47 and R 10 do not meet the designed uplift as supplied
by truss manufacture.
05-09-05wjd
Item not addressed.
07-18-05wjd
Cannot find Sheet S-4.04, Please submit. Item still not addressed.
|
2/2/2006
| WJD |
|
|
24. Truss data sheets and truss layout need to correlate. Quantity shown for Truss R3
appears incorrect. Can't find truss R51 on truss layout. Can't find truss data sheet for
R 57 shown on layout.
05-09-05wjd
Item not addressed.
007-18-05wjd
After review of the newly submitted truss layout and data sheet here is a list of things to correct.
Check Quantity comparison between truss layout and truss data sheet for the following.
R6A – 2 vs. 4
R27 – 3 vs. 7
R33C – Not found
R 34 – too many on layout
R 29 – no data sheet
R 41 - 12 vs. 8
R 44 – Not found
T4 – 6 vs. 2
T5 – 2 vs. 4
T9 – 16 vs. 2
T10 - 5 vs. 4
T11 - Not found
T12 - Not found
Please check overall truss length on R43
|
2/2/2006
| WJD |
|
|
25. Product of approval needs to specify limitations of use. In addition, please specify
M.D. NOA number for soffit.
05-09-05wjd
Item not addressed.
|
7/18/2005
| WJD |
|
|
26. Cannot find H15.07 as indicated next to detail on Sheet E16.03
05-09-05wjd
Item not addressed.
|
7/18/2005
| WJD |