Clearance Sheet C2004-005137

 Department IssuesSigned OffIntl
Plans APPROVED 12/6/2004 ROD
3. The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required. 12/6/2004 ROD
Please post the Occupant Load in a visible location within the building. 12/6/2004 ROD
Air handles with more than 2000 CFM is required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required) 12/6/2004 ROD
FYI: Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s). 12/6/2004 ROD
Please consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061) 12/6/2004 ROD