NO PLAN REVIEW THIS PACKAGE IS NOT COMPLETE MUST SUBMIT SIGNED AND SEALED DRAWINGS FOR THE PRE-ENGINEERED STEEL BUILDING  
Your re-submittal may include new pages, YOU must insert the revised pages into the three (3) sets of plans.. The “job copy” set of the original pages (removed pages) shall be re-submitted. ALL ITEMS REVISED SHALL BE IDENTIFIED. ADDITIONAL ITEMS MAY BE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW PLANS MUST BE LEGIBLE. Documents will be electronically scanned in order to produce a final record; therefore all documentation shall be clean, clear and with sufficient density, having enough contrast to produce an acceptable scanned image. AS PER ORDINANCE # 98-42 “An additional fee due and payable at permitting shall be of $100 each for any second re-submission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent re-submissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.  
1) Provide electrical plans and locate electrical panels on drawings. Drawing E-1 noted on title page is not in the package.  
2) Provide the engineering and drawings for the concrete tilt-up walls.  
3) This occupancy is required to have a service sink per the Florida Plumbing Code, the janitor sink being removed in the area of remodeling must have a replacement located somewhere in the building.