| | Department Issues | Signed Off | Intl |
|
|
Plan APPROVED for adding 2 (1 hour) fire walls and new bathroom in existing warehouse not protected with fire sprinklers of 9 suites. This will be reviewed under 2007 Fl Fire Prevention Code.
|
5/13/2011
| smurray |
|
|
QUESTIONS THAT MAY TRIGGER SPECIAL CONSIDERATION FOR STORAGE OCCUPANCIES Please write YES or NO on each line then complete below. This info must accompany the plans. _____Will you allow STORAGE OF HIGH-PILED COMBUSTIBLES over 12 feet high in areas greater than 2500 sq ft? _____Will you allow GROUP A PLASTICS STORAGE in excess of 5 ft in height over an area exceeding 2500 sq ft in area? _____Will you allow RUBBER TIRE STORAGE? _____Will you allow RECORD STORAGE? _____Will you allow CELLULOSE NITRATE MOTION PICTURE FILM STORAGE? _____Will you allow AEROSOL PRODUCTS STORAGE? _____Will you allow FLAMMABLE&COMBUSTIBLE LIQUID STORAGE? _____Will you allow PORTABLE LP-GAS CONTAINERS storage inside the bldg? _____Will you allow OXIDIZER STORAGE? _____Will you allow ORGANIC PEROXIDES STORAGE? 5/13/11-Applicant stated NO to all questions.
|
5/13/2011
| smurray |
|
|
(Please identify on the plans) 1. Identify the commodity of product to be stored. 2. Identify the type storage (racks, pallets, open floor, piles) and arrangement within the storage area of the building. 3. Identify a 36-inch wide aisle that will lead you to the exit. 4. Identify shipping or receiving areas on the plans. Any other operational areas will also have to be identified.
|
5/13/2011
| smurray |