| | Department Issues | Signed Off | Intl |
|
|
AS PER ORDINANCE # 98-42 “An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.
Plans must be legible. Documents will be electronically scanned in order to produce a final record; therefore all documentation shall be clean, clear and with sufficient density, having enough contrast to produce an acceptable scanned image.
|
11/29/2005
| MLR |
|
|
1. A outside electrical discount is required.
10/19/05: The outside discount on sheet E-2 is a 1000 amp discount. The total demand load for the building per sheet E-9 is 1102.51 amp need a 1200 amp discount and service.
|
11/29/2005
| MLR |
|
|
2. Provide a legable and scanable copy of 2 nd. floor rebar plan from Malone Steel. (need two complete sets of plans only one set provide for review)
10/19/05: Still missing one foundation plan for building F.
|
10/19/2005
| MLR |
|
|
3. The plan from Atlantic Steel Inc. submitted for review does not match the structural plans submitted for review.
|
10/19/2005
| MLR |
|
|
4. The Hambro drawing submitted for review are missing concrete beams at lines A, B & C at walk way.
|
10/19/2005
| MLR |
|
|
5. The conductors and main discount are under size for units D & E per load calculations on sheet E-9.
|
11/29/2005
| MLR |