SJC Home
Clearance Sheet C2004-000071*006

 Department IssuesSigned OffIntl
These plans are for a 15 device fire alarm system. The plans are APPROVED as submitted, with a comment below. 2/8/2006 PJW
Ensure that the audible signals have a sound level of at least 15 db. above average ambient sound level or 5 db. above the maximum sound level having at least 60 second duration, throughout all occupiable areas. Areas in question will be verified at the time of final. NFPA 72 7.4.2.1. 2/8/2006 PJW