| | Department Issues | Signed Off | Intl |
|
|
These plans are for a 12 unit condominium, reviewed under the new Apartments occupancy chapter. The plans are APPROVED as submitted.
|
4/14/2005
| PJW |
|
|
Any reference to the Fire Alarm in these plans are conceptual. A separate permit is required by the Fire Marshal. A HOLD will be placed on the building permit and NO FRAMING INSPECTION will be done until this permit is submitted & approved.
|
4/14/2005
| PJW |
|
|
Secondary means of escape are required from each sleeping and living area per NFPA 101 24.2 as referenced by NFPA 101 30.2.1
|
4/14/2005
| PJW |
|
|
3. The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required.
|
4/14/2005
| PJW |
|
|
Please consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061)
|
4/14/2005
| PJW |
|
|
FYI: Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s).
|
4/14/2005
| PJW |