Clearance Sheet C2004-000071*004

 Department IssuesSigned OffIntl
Arch.Name: Dixon Aso. Phone # 904-829-9277 Lic. # 149 Stru Eng.Name:Brackett & Asso. Phone # 904-821-78 Lic. # 42319 Name: Alan T. Ozell Phone # Lic. # 5983 Elec. Eng.Name: Davvid Hunter Phone # Lic. # 53375 Mech Plum. Eng.: Suzzanneeee LeViseur Lic. # Building Use: Apartmentss Occp Type: R2 Occp. Load: Const. Type: VI Spkl.: No Stories: 2 Area Separation: Occp. Separation Rated Corridors: Floor Area 1st : 2nd Your resubmittal should include three sets of plans or you may insert the revised pages into the plan sets and one set of the original shall be resubmitted. ALL ITEMS REVISED SHALL BE IDENTIFIED. ADDITIONAL ITEMS MAYBE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW AS PER ORDINANCE # 98-42 “ An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.  
1. Engineer of record needs to approve truss engineering.[ per Rule 61G15-30.006(3) ] (NO REVIEW DONE ON TRUSS ENGINEERING) 5/11/2005 MLR
2. Provide a truss layout that can be read and scaned into computer. ( full size sheet) 5/11/2005 MLR
3. Provide product approval numbers on product approval form. 05/11/05: Provide the Florida product approval numbers on St Johns County approval specification sheet.  
4. The roof layout plans for building type 1 & 2 calls for a connector # 6 provide information for that connector. 5/11/2005 MLR
5. Provide signed and sealed plan for Gate concrete floor slab for construction. (approved by engineer of record) 5/11/2005 MLR
FYI The Building Valuation is based on the data compiled by SBCCI & ICC using the Marshall Valuation Service as published by the Marshall and Swift Publication Company and printed in the Southern Builder  
FYI THIS ISSUES REOPRT IS FOR BUILDING 4 THUR 9