These plans are for a 54 device fire alarm system for a Class A Mercantile Occupancy. The plans are REJECTED for the following reasons.
|
| |
|
|
The entire fire alarm drawing was submitted using 1/16 scale. The only means that I have to read 1/16 scale is a plan wheel. If possible please design the drawings using a more common architectural scale ie/ 1/8, or 1/4 scale. Per a phone conversation with the designer, the dimensions that CAD shows do not correspond with the distances I am showing with my scale. It appears that there may be an issue with the plotting of the drawing. Please resubmit showing proper scale (NFPA 1:1.14)(NFPA 72:4.5.1.1.) Plan REJECTED.
|
| |
|
|
A sealed Design Criterion for the fire alarm system over $5000.00 is required for the building permit. (FBC 105.3.1.2(5) We are unable to approve the plan until this information is provided. THIS IS WHAT IS REQUIRED BY ADMINISTRATIVE CODE 61G15-33.006,(A-F) Common Requirements to All Fire Protection Engineering Documents.
|
| |
|
|
Please indicate how the live voice public address system announcements are to be made per NFPA 101 37.3.4.3.1.(2)(a). Please indicate where it will be located on the plans.
|
| |