SJC Home
Clearance Sheet C2003-005489*001

 Department IssuesSigned OffIntl
INFORMATIONAL: These plans are new plans for a project that has been reviewed before. The plans are for a 3000 square foot office warehouse occupancy. The warehouse is 1600 square feet & the office is 1216 square foot. The storage occupancy at the time of plan review was to be used to store pumps & pump part. The building is 20 foot high, however according to the contractor there is to be no rack storage over 12 feet high. 6/9/2004 JJR
Post over the office and note on the plans "NO STORAGE OVER OFFICE) 6/9/2004 JJR
The following conditions where written on the plans and aggreed upon by the contractor, and will be subject to final field inspection: - There needs to be a rear exit from the storage area. (you could modify the office layout and use the rear door there.(NFPA 101,42.2.4.1)Remember there nees to be a level platform/pad as you step out of the rear door as required in the building code. - You need to show a 36 inch aisle in the storage area. This can be taped or painted or the rack in place with the aisle(s) clearly identified. This comment is subject to a final field inspection. (if the floor plan page is replaced with a new page this 36" aisle needs to be shown on the plan.) - Post over the office and note on the plans "NO STORAGE OVER OFFICE" 6/9/2004 JJR