| | Department Issues | Signed Off | Intl |
|
|
Plans APPROVED.
|
2/25/2004
| ROD |
|
|
3. The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required.
|
2/25/2004
| ROD |
|
|
All doors that have dead bolts shall use thumb type single cylinder.
|
2/25/2004
| ROD |
|
|
Air handles with more than 2000 CFM is required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required)
|
2/25/2004
| ROD |
|
|
FYI: Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s).
|
2/25/2004
| ROD |
|
|
Please consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061)
|
2/25/2004
| ROD |