| | Department Issues | Signed Off | Intl |
|
|
1. E1.1 Provide revised riser diagram. a. Provide exterior disconnect b. Revise conduit size to comply with NEC chapter 9 tables.
|
6/26/2006
| JNP |
|
|
2. Provide hood drawings to comply with FBCM 507 and 508.
Monday, June 26, 2006 Item remains open: Please provide hood drawings to comply with FBCM 507 and 508.
|
7/11/2006
| JNP |
|
|
3. Provide complete HVAC equipment schedule.
Monday, June 26, 2006 Received partial equipment schedule, still need total cooling, sensible cooling, heating, CFM, and outside air
|
7/11/2006
| JNP |
|
|
4. Provide outside air per FMC Table 403.3.
Monday, June 26, 2006 Received outside air calculations from Table 403.3, please revise duct drawing and show outside air.
|
7/11/2006
| JNP |
|
|
5. Provide 2-hour listed penetrations for electrical and plumbing entering the tenant separation wall.
|
7/11/2006
| JNP |