Clearance Sheet C2003-005472*002

 Department IssuesSigned OffIntl

1.  E1.1  Provide revised riser diagram. a. Provide exterior disconnect  b. Revise conduit size to comply with NEC chapter 9 tables.

6/26/2006 JNP

2.  Provide hood drawings to comply with FBCM 507 and 508.

Monday, June 26, 2006  Item remains open:  Please provide hood drawings to comply with FBCM 507 and 508.

7/11/2006 JNP

3.  Provide complete HVAC equipment schedule.  

Monday, June 26, 2006  Received partial equipment schedule, still need total cooling, sensible cooling, heating, CFM, and outside air 

 

7/11/2006 JNP

4.  Provide outside air per FMC Table 403.3.

Monday, June 26, 2006  Received outside air calculations from Table 403.3, please revise duct drawing and show outside air.

7/11/2006 JNP

5.  Provide 2-hour listed penetrations for electrical and plumbing entering the tenant separation wall.

7/11/2006 JNP