 Department IssuesSigned OffIntl
These plans are for a 3960 square foot dentist office. The plans were reviewed using the 2004 Florida Fire Prevention Code New Business occupancy chapter. The plans are APPROVED as submitted with some informational comments below. 1/19/2006 PJW
See attached fax for exit sign locations for this space. 1/19/2006 PJW
The elevation of the floor surface on both sides of a door shall not vary by more than a 1/2 inch, and shall be maintained on both sides of the door for a distance not less than the width of the widest leaf. NFPA 101 7.2.1.3. 1/19/2006 PJW
All doors that have dead bolts shall use thumb type single cylinder. 1/19/2006 PJW
Air handles with more than 2000 CFM is required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required) 1/19/2006 PJW
FYI:Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". 1/19/2006 PJW
Consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061) 1/19/2006 PJW