Clearance Sheet C2003-004533*008

 Department IssuesSigned OffIntl

1.  Please provide a one-hour listed penatration for the electrical and phone wiring entering the tenant separation wall.
 
Wednesday, July 14, 2010  Item remains open: Please provide a cutsheet for a one-hour listed penatration. UL Online Certification Directory, 3M Fire Protection Products, or Hilti are sources that contain this information.


 

2.  Sheet E01 shows an outside 125 amp main breaker and a 2" empty conduit stubbed to suite 2C. Please revise the electrical riser diagram to show the sub-panel and the feeder wire sizes.(Indicate aluminum or copper conductors)