| | Department Issues | Signed Off | Intl |
|
|
#1
same comment per fac 61g15-30.005 arch of record must stamp reviewed & approved truss layout / inventory sheets . truss layout
inventory sheet is not legible for inspector and no layout by architect on plans
|
9/10/2015
| fbecza |
|
|
#2
provide covered walkway connections to bldg. with flashing details [same comment as previous review]
|
9/10/2015
| fbecza |
|
|
#3
need correct occupancy "e" on plans with occupant load corrected per florida bldg. code section 305 and 1004.1.2
need note on cover sheet from approved development plan that states ancillary use to church not for weekday school or day care
|
7/30/2015
| fbecza |
|
|
#4
show all fire / smoke walls on plans with detail and fire / & smoke damper locations with detail on plans
|
9/10/2015
| fbecza |