#1

same comment per fac 61g15-30.005 arch of record must stamp reviewed & approved truss layout / inventory sheets . truss layout

inventory sheet is not legible for inspector and no layout by architect on plans

9/10/2015 fbecza

#2

provide complete foundation / footing plan with sections and all locations on plans that match truss drawings with all beams ,

headers with all connections also cast crete bearings and slab step down detail [same comment as previous review]

9/10/2015 fbecza

#3

provide covered walkway connections to bldg. with flashing details [same comment as previous review]

9/10/2015 fbecza

#4

per plumbing code 708.3.5 there shall be a 2way cleanout at the junction of the bldg. drain and sewer connection [same comment]

9/10/2015 fbecza

#5

need correct occupancy "e" on plans with occupant load corrected per florida bldg. code section 305 and 1004.1.2

9/10/2015 fbecza

#6

show all fire / smoke walls on plans with detail and fire / & smoke damper locations with detail on plans 

9/10/2015 fbecza