| | Department Issues | Signed Off | Intl |
|
|
#1
same comment per fac 61g15-30.005 arch of record must stamp reviewed & approved truss layout / inventory sheets . truss layout
inventory sheet is not legible for inspector and no layout by architect on plans
|
9/10/2015
| fbecza |
|
|
#2
provide complete foundation / footing plan with sections and all locations on plans that match truss drawings with all beams ,
headers with all connections also cast crete bearings and slab step down detail [same comment as previous review]
|
9/10/2015
| fbecza |
|
|
#3
provide covered walkway connections to bldg. with flashing details [same comment as previous review]
|
9/10/2015
| fbecza |
|
|
#4
per plumbing code 708.3.5 there shall be a 2way cleanout at the junction of the bldg. drain and sewer connection [same comment]
|
9/10/2015
| fbecza |
|
|
#5
need correct occupancy "e" on plans with occupant load corrected per florida bldg. code section 305 and 1004.1.2
|
9/10/2015
| fbecza |
|
|
#6
show all fire / smoke walls on plans with detail and fire / & smoke damper locations with detail on plans
|
9/10/2015
| fbecza |