Clearance Sheet C2003-004116*017

 Department IssuesSigned OffIntl

#1

provide florida accessibility detail sheet with all turning radius , clearances , reaches and component heights

7/16/2015 fbecza

#2

show on plan tables , chairs or open area with correct occupant load for multi-purpose rm.

7/16/2015 fbecza

#3

show / note on plans the classrooms are to be used for educational purposes k thru 12th grade and the multi purposes room will be

used for a religious auditoriums or religious educational purposes / assembly areas that are accessory to group 'e' occupancy are

not considered a separate occupancy except the occupant load is calculated as assembly per fbc 303 and 305

7/16/2015 fbecza

#4

provide door , hardware and finish schedules on plans / per fbc 1210 rest room walls and floors shall have a smooth , hard ,

nonabsorbent surface

7/16/2015 fbecza

#5

per fbc 1006 show emergency lighting in corridors and they shall be illuminated to at least 1 footcandle measured at the floor

7/16/2015 fbecza

#6

need location of  service , panel schedule [ circuit layout ] load calcs list 2 ranges [ not shown on plans ?] , need locations of

ahu disconnects with outlets and lighting

7/16/2015 fbecza

#7

per fmc 306 show ahu access and service space [working platform] condensate disposal .                               

per florida energy code 503.2.7 ahu's not allowed in attics / provide enclosure around units [see attic definition] fec 202

7/16/2015 fbecza

#8

show required cleanouts on plumbing riser diagram

9/10/2015 fbecza

#9

provide covered walkway connection details

9/10/2015 fbecza

#10

arch.of record must stamp & sign truss inventory / layout review approval 

9/10/2015 fbecza

#11

provide complete footing plan with sections that show locations and details of all bearing walls that match truss dwgs. with all beams ,

headers with connections also cast crete bearings & slab step down detail

9/10/2015 fbecza