| | Department Issues | Signed Off | Intl |
|
|
#1
provide florida accessibility detail sheet with all turning radius , clearances , reaches and component heights
|
7/16/2015
| fbecza |
|
|
#2
show on plan tables , chairs or open area with correct occupant load for multi-purpose rm.
|
7/16/2015
| fbecza |
|
|
#3
show / note on plans the classrooms are to be used for educational purposes k thru 12th grade and the multi purposes room will be
used for a religious auditoriums or religious educational purposes / assembly areas that are accessory to group 'e' occupancy are
not considered a separate occupancy except the occupant load is calculated as assembly per fbc 303 and 305
|
7/16/2015
| fbecza |
|
|
#4
provide door , hardware and finish schedules on plans / per fbc 1210 rest room walls and floors shall have a smooth , hard ,
nonabsorbent surface
|
7/16/2015
| fbecza |
|
|
#5
per fbc 1006 show emergency lighting in corridors and they shall be illuminated to at least 1 footcandle measured at the floor
|
7/16/2015
| fbecza |
|
|
#6
need location of service , panel schedule [ circuit layout ] load calcs list 2 ranges [ not shown on plans ?] , need locations of
ahu disconnects with outlets and lighting
|
7/16/2015
| fbecza |
|
|
#7
per fmc 306 show ahu access and service space [working platform] condensate disposal .
per florida energy code 503.2.7 ahu's not allowed in attics / provide enclosure around units [see attic definition] fec 202
|
7/16/2015
| fbecza |
|
|
#8
show required cleanouts on plumbing riser diagram
|
9/10/2015
| fbecza |
|
|
#9
provide covered walkway connection details
|
9/10/2015
| fbecza |
|
|
#10
arch.of record must stamp & sign truss inventory / layout review approval
|
9/10/2015
| fbecza |
|
|
#11
provide complete footing plan with sections that show locations and details of all bearing walls that match truss dwgs. with all beams ,
headers with connections also cast crete bearings & slab step down detail
|
9/10/2015
| fbecza |