| | Department Issues | Signed Off | Intl |
|
|
Arch.Name: J. Douglas Snead Jr. Phone # 904-720-2669
Lic. #
Eng.Name: Jimmy P. Cochran Phone #
Lic. # 54925
Occp Type: D Const. Type: IV Spkl. : Yes Occp. Load: 148
Your resubmittal should include three sets of plans or you may insert
the revised pages into the plan sets and one set of the original shall
be resubmitted. ALL ITEMS REVISED SHALL BE IDENTIFIED.
ADDITIONAL ITEMS MAYBE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF
FINAL PLANS SUBMITTED FOR REVIEW
AS PER ORDINANCE # 98-42 “ An additional fee due and payable at permitting shall
be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)
(b), on any third and subsequent resubmissions that do not correct a code violation
that is specifically and continuously noted in each previous rejection, a fee of
four times the amount of the fee attributed to plan review will be charged.
|
10/8/2003
| MLR |
|
|
1. Missing diameter of anchor bolts and lenght.
|
9/24/2003
| MLR |
|
|
2. Glazing in frame C for door #43 need to be comply with section
705.1.3 of the Florida Building Code.
|
9/24/2003
| MLR |
|
|
3. Provide 3 complete sets plans signed and sealed drawing for storefront.
|
| |
|
|
4. Missing information on the exterior 6” metal studs.( gauge of metal studs, fastener
for top and bottom tract)
|
9/24/2003
| MLR |
|
|
5. Provide design criteria for building. (i.e.: wind load, exposure,
partially enclosed or enclosed, soil bearing, live and dead loads etc.)
|
9/24/2003
| MLR |
|
|
6. Missing information on the interior metal studs.( gauge of metal studs, fastener
for top and bottom tract)
|
9/24/2003
| MLR |
|
|
FYI
Address comments by Fire Marshall
Provide approved site plan from DRC
|
10/8/2003
| MLR |
|
|
Provide the Fault Current Letter from the power company. No electrical permits
will be issued until submitted and approved.
|
10/8/2003
| MLR |