Plans call for the building of a early Childhood center. 8226 square foot building fully protected by sprinkler system. 8/8/2003 ROD
The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required. 8/8/2003 ROD
All doors that have dead bolts shall use thumb type single cylinder. 8/8/2003 ROD
Please post the Occupant Load in a visible location within the building. 8/8/2003 ROD
FIRE LANES shall be marked with free standing signs with the words "NO PARKING FIRE LANE BY ORDER OF THE FIRE DEPARTMENT." Such signs shall be 12" by 18" with a white background & red letters and shall be a minimum of 7-feet in height from the roadway to the bottom part of the sign. The sign shall be within sight of the traffic flow and be a maximum of 60 feet apart.(FPC 1.3.5.4)  
Air handles with more than 2000 CFM is required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required)  
The UNDERGROUND CONTRACTOR for the installation & hydro test of the fire sprinkler line will require a separate permit. A HOLD will be placed on the building permit and NO FIRE SPRINKLER FINAL will be done until this permit is submitted & approved.  
Provide a Knox Box near the main entrance. This box is required because there is a fire sprinkler riser located inside this building. An authorization form for the Knox Box can be obtained at the Fire Marshal's Office.(4455 Avenue "A", Suite 100, St Augustine, Phone 904-823-2709)  
FYI: Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s). 8/8/2003 ROD
Please consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061) 8/8/2003 ROD
Any reference to the Fire Alarm in these plans are conceptual. A separate permit is required by the Fire Marshal. A HOLD will be placed on the building permit and NO FRAMING INSPECTION will be done until this permit is submitted & approved.  
The Fire Sprinkler information provided in these plans are conceptual. A separate fire sprinkler permit is required by the Fire Marshal. A HOLD will be placed on the building permit and no framing inspection will be done until this permit is submitted & approved.  
Please provide a current water flow test for the area . The one noted in the plans is about 18 months old.