SJC Home
Clearance Sheet C2003-002286

 Department IssuesSigned OffIntl
Within the comments there will be items that need to be addressed before we can approve the permit, and comments that are informational. Informational comments will be started with "FYI", and will be signed off, any comment that will require your responce will start with "ACTION". 5/27/2003 ROD
Air handles with more than 2000 CFM is required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required)  
Provide a Knox Box near the main entrance. This box is required because there is a fire sprinkler riser located inside this building. An authorization form for the Knox Box can be obtained at the Fire Marshal's Office.(4455 Avenue "A", Suite 100, St Augustine, Phone 904-823-2709)  
FYI: Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s).  
Please consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061)  
Any reference to the Fire Alarm in these plans are conceptual. A separate permit is required by the Fire Marshal. A HOLD will be placed on the building permit and NO FRAMING INSPECTION will be done until this permit is submitted & approved.  
The Fire Sprinkler information provided in these plans are conceptual. A separate fire sprinkler permit is required by the Fire Marshal. A HOLD will be placed on the building permit and no framing inspection will be done until this permit is submitted & approved.