| | Department Issues | Signed Off | Intl |
|
|
Must submit an approved DRC site plan
|
8/8/2003
| CFB |
|
|
Provide a completed DRC clearance sheet for this project.
|
8/8/2003
| CFB |
|
|
Provide the Fault Current Letter from the power company. No electrical permits will
be issued until submitted and approved.
|
| |
|
|
Provide water/sewer availability letters.
|
8/8/2003
| CFB |
|
|
The Notice of Commencement must be submitted to the building dept. prior to any inspections.
|
8/8/2003
| CFB |
|
|
Plumbing fixtures are not vented properly. Provide a revised drawing.
Provide a trap primer for the floor drains to protect the trap seal.
8/8/03
This item has been addressed but not corrected, the floor drain is not vented
properly.
NOTE; THE NUMBER OF SANITARY FACILITIES REQUIRED FOR SWIMMING POOLS WILL BE
PER FPC SECTION 403.8. The number of required fixtures will depend on the
size of the swimming pool.
|
8/20/2003
| CFB |
|
|
Provide two (2) sets of truss drawings with a layout sheet. Layout sheet to be
signed by the engineer of record that the trusses meet his/her design requirements.
Provide a uplift connector schedule including number and size of the fasteners
for each connector.
8/8/03
This item has been addressed but is not complete.
|
8/20/2003
| CFB |
|
|
Provide the nail pattern and size of nails for the roof deck sheathing
and the wall sheathing.
|
8/8/2003
| CFB |
|
|
Provide a detail for the headers include the uplift and holddowns for the headers,
Provide the bracket and the fasteners to carry the headers.
8/8/03
This item has been addressed but no acceptable. Cut nails are not an approved
fastener for simpson hangers. Need to provide the uplift calcuations for the uplift
on the headers and must provide the hanger number for uplift.
|
8/20/2003
| CFB |
|
|
Show the dowels from the footer and the top of columns. Wood headers
to provide the lateral bracing?
|
8/8/2003
| CFB |
|
|
Provide an electrical riser diagram and the panel schedule, size the
conductors, and conduit. Type of conductors.
8/8/03
This item has been addressed but not complete.
See NEC 2002, i/0 conductors are not approved for 200 amps. Must state the
type of conductor insulation.
|
8/20/2003
| CFB |
|
|
Show the exhaust fans and duct for the restrooms. Include the CFM.
8/8/03
This item has been addressed, but is not correct.
See FMC for the minium CFM required for public restrooms.
|
8/20/2003
| CFB |
|
|
See FBC 1606.1.7 for the miniumn infromation required on the plans.
Building must be designed for 120 MPH.
8/8/03
This item has not been addressed as the plans have the building designed
for 110 MPH wind.
|
8/20/2003
| CFB |