Clearance Sheet C2003-002286*005

 Department IssuesSigned OffIntl
Must submit an approved DRC site plan 8/8/2003 CFB
Provide a completed DRC clearance sheet for this project. 8/8/2003 CFB
Provide the Fault Current Letter from the power company. No electrical permits will be issued until submitted and approved.  
Provide water/sewer availability letters. 8/8/2003 CFB
The Notice of Commencement must be submitted to the building dept. prior to any inspections. 8/8/2003 CFB
Plumbing fixtures are not vented properly. Provide a revised drawing. Provide a trap primer for the floor drains to protect the trap seal. 8/8/03 This item has been addressed but not corrected, the floor drain is not vented properly. NOTE; THE NUMBER OF SANITARY FACILITIES REQUIRED FOR SWIMMING POOLS WILL BE PER FPC SECTION 403.8. The number of required fixtures will depend on the size of the swimming pool. 8/20/2003 CFB
Provide two (2) sets of truss drawings with a layout sheet. Layout sheet to be signed by the engineer of record that the trusses meet his/her design requirements. Provide a uplift connector schedule including number and size of the fasteners for each connector. 8/8/03 This item has been addressed but is not complete. 8/20/2003 CFB
Provide the nail pattern and size of nails for the roof deck sheathing and the wall sheathing. 8/8/2003 CFB
Provide a detail for the headers include the uplift and holddowns for the headers, Provide the bracket and the fasteners to carry the headers. 8/8/03 This item has been addressed but no acceptable. Cut nails are not an approved fastener for simpson hangers. Need to provide the uplift calcuations for the uplift on the headers and must provide the hanger number for uplift. 8/20/2003 CFB
Show the dowels from the footer and the top of columns. Wood headers to provide the lateral bracing? 8/8/2003 CFB
Provide an electrical riser diagram and the panel schedule, size the conductors, and conduit. Type of conductors. 8/8/03 This item has been addressed but not complete. See NEC 2002, i/0 conductors are not approved for 200 amps. Must state the type of conductor insulation. 8/20/2003 CFB
Show the exhaust fans and duct for the restrooms. Include the CFM. 8/8/03 This item has been addressed, but is not correct. See FMC for the minium CFM required for public restrooms. 8/20/2003 CFB
See FBC 1606.1.7 for the miniumn infromation required on the plans. Building must be designed for 120 MPH. 8/8/03 This item has not been addressed as the plans have the building designed for 110 MPH wind. 8/20/2003 CFB