Job Name:Church on the Rock Job address:2995 Varella Ave.
Clearance Sht. #C03-1696 Flood zone: C
Contr. Name:Marvin Outley Phone # 904-392-5419
Lic. #
Arch. Name: Phone #
Lic. #
Eng. Name:Scott S. Francis Phone #
Lin. # 46911
Occp Type: A Const. Type: VI Spkl. :NO Occp.load: 238
Your resubmittal should include three sets of plans or you may insert
the revised pages into the plan sets and one set of the original shall
be resubmitted. ALL ITEMS REVISED SHALL BE IDENTIFIED.
ADDITIONAL ITEMS MAYBE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF
FINAL PLANS SUBMITTED FOR REVIEW
AS PER ORDINANCE # 98-42 “ An additional fee due and payable at permitting shall
be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)
(b), on any third and subsequent resubmissions that do not correct a code violation
that is specifically and continuously noted in each previous rejection, a fee of
four times the amount of the fee attributed to plan review will be charged.
|
| |
|
|
Foundation plan doesn’t match modular plans, drawing #1030V, Quote #1030
or serial no. 3233-35. Foundation plan needs to reference the above modular.
Need to provide sheet 1,2 & 3 of foundation plan.
|
12/11/2003
| MLR |
|
|
Provide an electrical isometric drawing.
12/12/03 Isometric doesn't match elec. floor plan of building. Plan show 3
100 amp panels please clarify.
|
| |
|
|
Provide stair details showing rise and run, handrails height
and spacing of intermediate rail per sections 1007 & 1015.3
of the FBC.
12/12/03 not submitted for review.
|
| |
|
|
Provide ramp details showing slope, handrails height
and spacing of intermediate rail per sections 11-4.8 of the FBC.
12/12/03 not submitted for review.
|
| |
|
|
Provide drinking fountains per section 11-4.1.3 (10) of the FBC.
|
12/12/2003
| MLR |