| | Department Issues | Signed Off | Intl |
|
|
Within the comments there will be items that need to be addressed before we can approve the permit, and comments that are informational. Informational comments will be started with "FYI", and will be signed off, any comment that will require your responce will start with "ACTION".
|
4/30/2003
| ROD |
|
|
Plans APPROVED with comments attached.
|
4/30/2003
| ROD |
|
|
FYI: Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s).
|
4/30/2003
| ROD |
|
|
Please consult with your fire extinguisher contractor for the portable fire extinguisher requirements for this occupancy.(FS 633.061)
|
4/30/2003
| ROD |
|
|
The Grease Exhaust Hood noted on this page and several other pages throughout these plans are conceptual. A separate permit will be required by the Fire Marshal. A HOLD will be placed on the building permit and NO FRAMING INSPECTION will be done until this permit is submitted & approved.
|
| |
|
|
Air handles with more than 2000 CFM is required to have duct smoke detectors. If these detectors are concealed they shall have a remote visual and audible indicators located in a normally occupied space. (NOTE if there is a FIRE ALARM SYSTEM in the building the duct smoke detector must also be connected to the fire alarm system. In those cases only a visual indicator is required)
|
4/30/2003
| ROD |
|
|
The Grease Exhaust Hood requires a FIRE SUPPRESSION SYSTEM. The Fire Marshal's Office requires a separate permit and a HOLD will be placed on the building permit whereby NO FRAMING INSPECTION AND NO FINAL EXHAUST HOOD INSPECTION can be done until this permit is approved.
|
| |