PLan APPROVED for add/replace 10 devices on existing fire alarm system.
|
11/9/2015
| SMurray |
|
|
Ensure that the audible signals have a sound level of at least 15 db. above average ambient sound level or 5 db. above the maximum sound level having at least 60 second duration, throughout all occupiable areas. Areas in question will be verified at the time of final. (NFPA 72 18.4.5)
|
11/9/2015
| SMurray |
|
|
All fire alarm system strobe lights shall be 75 minimum candela per State Fire Marshal's Dec statement Sneed 80599-05-FM.
|
11/9/2015
| SMurray |