AS PER ORDINANCE # 98-42 “An additional fee due and payable at permitting shall be of $100 each for any second resubmission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent resubmissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.
|
12/7/2004
| MLR |
|
|
1. The following information is required for kitchen hood and duct application. For this specific job site.
a.) Provide duct enclosure and testing agency information per section 506.3.12 of the Florida Mechanical Code.
b.) Missing the air velocity within the duct system. per section 506.3.6 of the Florida Mechanical Code.
c.) Provide clearance for hood per section 507.9 of the Florida Mechanical Code.
d.) Provide floor plan of equipment under hood and show size of canopy comply with per section 507.12 of the Florida Mechanical Code.
f.) Provide calculations showing capacity of hood per section 507.13 of the Florida Mechanical Code.
|