Clearance Sheet C2002-004924*001

 Department IssuesSigned OffIntl
1) Your re-submittal should include three sets of plans or YOU may insert the revised pages into the plan sets and one set of the original shall be re-submitted. ALL ITEMS REVISED SHALL BE IDENTIFIED. ADDITIONAL ITEMS MAYBE REQUIRED - DEPENDING ON INFORMATION AND CLARITY OF FINAL PLANS SUBMITTED FOR REVIEW AS PER ORDINANCE # 98-42 “ An additional fee due and payable at permitting shall be of $100 each for any second re-submission of plans. Per FL. Statute 553.80(2)(b), on any third and subsequent re-submissions that do not correct a code violation that is specifically and continuously noted in each previous rejection, a fee of four times the amount of the fee attributed to plan review will be charged.  
2) This is a threshold building as defined in Florida Statute 553.71, the requirements as described in FS 553.79 are required for review and prior to a permit being issued. The plans shall contain a statement as required in FS 553.797(d). 2/12/04 This item was addressed but not complete. Must provide the structural inspection plan from the Structural Engineer of Record, as required per FS.553.79 and the name and license number of the "Special Inspector".  
3) Provide the Fault Current Letter from the power company. No electrical permits will be issued until letter is submitted and approved. 2/12/2004 CFB
4) The truss drawings must be reviewed by the Engineer of Record and the layout sheet signed by EOR that the trusses meet his/her design requirement for this building. Need the layout sheet for the roof and floor trusses. The design loads for the floor trusses must meet FBC chapter 16.) 2/12/04 This item was addressed but not complete. The EOR must review the truss drawings and sign the layoutr sheet. Need to submit 1 set of truss drawings with raised seal.  
5) Need to provide the length and miminum penatration of the #10 screws shown in details. 2/12/2004 CFB
6) Provide the manufacturer's installation instructions with the required size of the combustable air duct for the water heater to be installed. 2/12/2004 CFB
7) Must provide a service sink for this occupancy. The sink listed on isometric, (P-4), has been deleated in the fixture schedule. 2/12/2004 CFB
8) Exit access corridors must be rated one (1) hour as per FBC 704.2.4. Provide the UL number for the walls and ceiling that will be used to comply. 2/12/2004 CFB
9) Provide draftstopping as per FBC 2305.2 for this building. 2/12/2004 CFB
10) Must provide a four (4) hour fire rated assembly in the roof of the covered walk that joins this building to the existing building. Only one electrical service permitted to a building; the buildings must be completely separate, or provide a four hour rated assembly to provide the separation required. 2/12/04 The building has been moved to provide the required separation. 2/12/2004 CFB
12) Must address the fire department comments before plans approval. 2/12/2004 CFB
Must submit an approved DRC site plan, (stamped approved) including the changes.