Plan submitted for build out of 4970sf in an existing construction type IIb building with 1 hour tenant separations. Reviewed as mercantile class c using FFPC 7th edition effective January 1, 2021.
Reviewer: V.Vitori 904 209 1748
To schedule fire inspections please call 827-6842 (automated system). Questions about inspections please call 209-1740x1. Review by the AHJ shall not relieve the applicant of the responsibility for compliance with the Code.
|
4/30/2021
| VVitori |
|
|
Page E1.0 indicates emergency lights are to be put on unswitched circuit. 101:7.9.2.3(3) requires emergency lights to come on when accidental opening of a switch controlling normal lighting.
|
4/30/2021
| VVitori |
|
|
INFORMATIONAL ONLY NO RESPONSE NECESSARY: The system(s) outlined in this set of plans is conceptual.
A HOLD has been placed at insulation inspection (109) until either: a) a permit has been pulled or b) a letter submitted from respective system contractor indicating no work to be done to the existing system:
- Fire sprinkler system
|
4/30/2021
| VVitori |