Clearance Sheet C2000-000251*002

 Department IssuesSigned OffIntl

Plan APPROVED for interior remodel from a bank to a 4815 sqft dentist office. This is reviewed under 2010 Fl Fire Prevention Code as business.
There will be a separate inspection by a third party for the med gas.

5/7/2012 smurray
Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". (NFPA 1, 10.12.1.2) 5/7/2012 smurray
Locks on exit doors or access exit doors shall not require the use of a key, a tool, or special knowlege or effort for operation from the egress side unless they meet the requirements of NFPA 101, 7.2.1.5. 5/7/2012 smurray

If this is light-weight truss-type construction (repetitive wood  or light guage steel framing) placement of approved Firefighting Safety Warning Sign (Maltese Cross) shall be placed on structure in accordance with FS 633.027 and FAC 69A-60.008 (size, color, height placement)

5/7/2012 smurray
FS 633.061 requires a license or permit of organizations & individuals who: service, recharge, test, mark, inspect, install or hydrotest fire extinguishers. It will be necessary to use a Licensed Fire Extinguisher Contractor for identifying the location & type of extinguisher to use. 5/7/2012 smurray