SJC Home
Clearance Sheet C2000-000128*001

 Department IssuesSigned OffIntl

Plan APPROVED to add 1023 sqft and remodel part of the 2 story clubhouse for a fitness center inside a bldg protected with fire sprinklers and fire alarm. This is reviewed under 2010 Fl Fire Prevention Code as assembly.

4/5/2013 smurray
The scope of work for this project is in the area of an existing fire sprinkler and fire alarm system. A separate fire sprinkler and fire alarm permit is required for any modification to this system. A hold is placed on the Building Permit and no inspections past framing will be done until this Fire Sprinkler and Fire Alarm Permit is submitted & approved. (NFPA 1,13.1.1.1) 4/5/2013 smurray
Please provide building numbers that are a minimum of 6-inches high on the building and/or suite(s) for commercial. These must be visible and legible from the street, therefore the address number may need to be larger than the minimum 6". (NFPA 1, 10.12.1.2) 4/5/2013 smurray

All exit doors except front doors require panic hardware. NFPA 101, 13.2.2.3

4/5/2013 smurray
The emergency lights are required to provide 1-footcandle of illumination on the floor along the exit path. This requirement is subject to a performance test conducted prior to the final. Additional Lights may be required. (NFPA 101, 7.8.1) 4/5/2013 smurray