#1

see fire review comments

3/2/2017 fbecza

#2

per fbc chapter 311 use is s-1 storage [repair garage]

3/2/2017 fbecza

#3

2011 nec current code in effect / need on cover sheet 

3/2/2017 fbecza

#4

per fbc chapter 1 a life safety plan is required 

3/2/2017 fbecza

#5

per nec 110.16 arc-flash hazard warning required on switchboards , panel boards shall be field marked and per 110.18 parts of electrical equip. that in ordinary operation produce

arcs , sparks , etc. shall be enclosed or separated and isolated .

3/2/2017 fbecza

#6

per fpc 403.1 and 411 an emergency eye wash station is required

3/2/2017 fbecza

#7

show location of welder on plan

3/2/2017 fbecza

#8

provide written response to all review comments

3/2/2017 fbecza