Plan REJECTED for 4500 repair garage going to be converted to service CHG repair vehicles. Reviewed using FFPC 5th edition. NFPA 1 ch 30 and NFPA 52

Reviewer: Sandra Boike 904 209 1741  sboike@sjcfl.us

To reply to comments and/or resubmit plans, contact your permit tech via their email or call 904-827-6800. To help speed the review process you may include a written comment response summary to clarify or illustrate where corrections were made on plans.  Please remember to use the Florida Fire Prevention Code 5th Ed for all code reference in a response to comments. The fire plans examiner does not use or have a copy of the Florida Building Code.

To schedule your fire inspection please call 904 209 1740x1.

------------------------------------

Thursday, February 23, 2017

Px Eric this morning about the hazard classification.

---------------------------------------

Tuesday, February 28, 2017

Reviewed with NO PENDING comments.

2/28/2017 sboike

NFPA 1.30.2.4 Means of egress. Please provide illustrate exit identification.

----------------------------

Tuesday, February 21, 2017

Response: Exit signs have been added in sheet F1.0

 

2/23/2017 sboike

NFPA 1.30.2.8. Gas detection, please provide manufacture cut sheets for the components of the detection systems. Please provide order of operation of the system.

-----------------------

Thursday, February 23, 2017

Addressed on F1.0

2/23/2017 sboike

NFPA 1.30.2.8.4 Monitoring of the detection system shall be in accordance with NFPA 72. How are you meeting this?

---------------------------------

Thursday, February 23, 2017

Response: The sensors will be installed within the classified zone. The sensors are compliant for class1 division 2

2/23/2017 sboike

Could not locate return air openings? NFPA 1.30.2.9.2

---------------------------

Thursday, February 23, 2017

Response: The system is designed as exhaust only. Therefore, there are no return openings in the b uilsing. Please see sheet M3.1 for the location of EF-1,2,3.

2/23/2017 sboike

Will there be any containers to store the NG during repair or will there be a process of removing/ refueling the equipment? NFPA 52.4

-------------------------------------

Thursday, February 23, 2017

Response: There will be no refueling and defueling process inside of the repair garage. There will be no natural gas containers stored inside of the repair garage.

2/23/2017 sboike

Is there a 2 hr separation from the repair/ storage of the vehicles containing NG and the other rooms? NFPA 52.8.4.3.4.2 

--------------------------------

Thursday, February 23, 2017

Response: NFPA 52 chapter 8 deals with processing, storing and dispensing CNG. CNG will not be processed, stored or dispensed at this facility. Therefore, we feel that NFPA 52.8.4.3.4.2 does not apply.

2/23/2017 sboike

How are you compiling with NFPA 52.8.4.3.4.5 or 8.4.3.4.6?

---------------------

Thursday, February 23, 2017

Response: See previous response.

2/23/2017 sboike

Please illustrate the placement of fire extinguishers. NFPA 1.30.3.2.2 and NFPA 58.8.15

-----------------------------

Thursday, February 23, 2017

Response: Addressed on plan F1.0

2/23/2017 sboike

Hazard Classification appears to have changed. Please provide classification from the design professional in accordance with NFPA 101.40.1.5, NFPA 101.6.2. This may trigger additional requirements.

-----------------------------------------

Tuesday, February 28, 2017

Reviewer called Eric about the hazard classification. He stated they will be doing basic maint. This is why they stated Ordinary Hazard. 

2/28/2017 sboike