| | Department Issues | Signed Off | Intl |
|
|
#1
see fire review comments
|
3/2/2017
| fbecza |
|
|
#2
per fbc chapter 311 use is s-1 storage [repair garage]
|
3/2/2017
| fbecza |
|
|
#3
2011 nec current code in effect / need on cover sheet
|
3/2/2017
| fbecza |
|
|
#4
per fbc chapter 1 a life safety plan is required
|
3/2/2017
| fbecza |
|
|
#5
per nec 110.16 arc-flash hazard warning required on switchboards , panel boards shall be field marked and per 110.18 parts of electrical equip. that in ordinary operation produce
arcs , sparks , etc. shall be enclosed or separated and isolated .
|
3/2/2017
| fbecza |
|
|
#6
per fpc 403.1 and 411 an emergency eye wash station is required
|
3/2/2017
| fbecza |
|
|
#7
show location of welder on plan
|
3/2/2017
| fbecza |
|
|
#8
provide written response to all review comments
|
3/2/2017
| fbecza |